  • INTRODUCTION

    Air to Water Heat Pump is a closed loop thermal device that draws heat from one place (called heat source) and reject the drawn heat to another place (called heat sink). Unlike conventional air to air heat pump, where generated thermal energy is used to cool/heat air fluid, Air to Water Heat Pumps use generated thermal energy to  cool/heat water or water/glycol fluid mixture. Our Monoblock Series Air to Water Heat Pumps can work at outdoor temperatures ranging between -20⁰C and +45⁰C.

    Features

    Control Protocol

    Our air to water heat pumps have Modbus protocol. Modbus is a communication protocol developed by Modicon systems. In simple terms, it is a method used for transmitting information over serial lines between electronic devices. Modbus is an open protocol, meaning that it is free for manufacturers to build into their equipment without having to pay royalties. It has become a very common protocol used widely by many manufacturers HVAC Equipment. Modbus is typically used to transmit signals from instrumentation and control devices back to a main controller or data gathering system.

    Modbus can be easily integrated with BACnet Controller either through BACnet/Modbus Gateways or simply by integrating the Modbus controller with the BACnet Controller (most BACnet controllers’ manufacturer have adapted their firmware to read Points Table of Modbus controllers).

    Control Interface & Control Cards

    Control interface is CAREL PGD1000 interface and Heat Pumps Controller are CAREL Controllers with Modbus Protocol.

    controller

    Compressors

    Compressors are Panasonic DC Inverter Twin Rotary Compressors. Panasonic uses high efficiency pump and environmentally friendly refrigerant, to achieve energy efficient and reliable rotary compressor designs. Panasonic has the smallest size variable speed rotary compressor in the industry. Panasonic rotary compressor has a good reputation with clients all over the world and are commonly used for room air conditioning and refrigeration.

    SPECIFICATIONS

    Model Number

    HSS060V2

    Properties

    SI

    Unit

    IP

    Unit

     

    Outdoor 86°F (30°) DB / 73°F (23°C) WB - Fluid Supply/Return Temperatures 44.6°F (7°C)/54.32°F (12°C)

    Nominal Cooling Capacity

    14.3

    KW

    48789

    BTU/HR

    COP / EER

    3.09

    KW Out /KW In

    MBH Out /KW In

    Min/Max Cooling Capacity

    6.6/14.35

    KW

    22518/48789

    BTU/HR

    Min/Max Power Input

    1.411/4.632

    KW

    1.411/4.632

    KW

    Min/Max COP / EER

    3.1/4.68

    KW Out /KW In

    10.6/16

    MBH Out /KW In

     

    Outdoor 95°F (35°) DB / 75°F (24°C) WB - Fluid Supply/Return Temperatures 44.6°F (7°C)/54.32°F (12°C)

    Nominal Cooling Capacity

    13.04

    KW

    44490

    BTU/HR

    COP / EER

    2.48

    KW Out /KW In

    8.47

    MBH Out /KW In

    Min/Max Cooling Capacity

    6.00/13.04

    KW

    20470/44490

    KW

    Min/Max Power Input

    1.668/5.264

    KW

    1.668/5.264

    KW

    Min/Max COP / EER

    2.48/3.6

    KW Out /KW In

    8.46/12.28

    MBH Out /KW In

     

    Outdoor 44.6°F (7°) DB / 42.8°F (6°C) WB - Fluid Supply/Return Temperatures 95°F (35°C)/86°F (30°C)

    Nominal Heating Capacity

    18.5

    KW

    63119

    BTU/HR

    COP

    4.39

    KW Out /KW In

    4.39

    KW Out /KW In

    Min/Max Heating Capacity

    8.51/18.5

    KW

    29035/63119

    BTU/HR

    Min/Max Power Input

    1.551/4.214

    KW

    1.551/4.214

    KW

    Min/Max COP

    4.39/5.49

    KW Out /KW In

    4.39/5.49

    KW Out /KW In

     

    Outdoor 44.6°F (7°) DB / 42.8°F (6°C) WB - Fluid Supply/Return Temperatures 113°F (45°C)/104°F (40°C)

    Nominal Heating Capacity

    17.4

    KW

    59366

    BTU/HR

    COP

    3.4

    KW Out /KW In

    3.4

    KW Out /KW In

    Min/Max Heating Capacity

    8.00/17.39

    KW

    27295/59366

    BTU/HR

    Min/Max Power Input

    1.918/4.952

    KW

    1.918/4.952

    KW

    Min/Max COP

    3.51/4.17

    KW Out /KW In

    3.51/4.17

    KW Out /KW In

    Power Supply (V/Ph/Hz)

    220-240/1/60

    Rated Current (Amp)

    20.2

    Maximum Current (Amp)

    29.24

    Refrigerant Type

    R410A

    Compressor

    Panasonic

    Condenser Fan Quantity

    2

    Condenser Fan Airflow

    5500

    m³/hr

    3235

    ft³/min

    Condenser Fan Rated Power

    210

    Watt

    210

    Watt

    Fluid Side Heat Exchanger Type

    Plate Heat Exchanger

    Fluid Side Pressure Drop

    25

    Kpa

    8.365

    ft of Water

    Piping Connection Size

    1"

    Allowable Water Flow (Min / Rated / Max)

    0.55/0.88/1.47

    L/s

    8.72/13.95/23.3

    US gpm

    Noise Level

    63

    Net Dimensions (LxDxH)

    1110x475x1355

    mm x mm x mm

    44x19x54

    in x in x in

    Packaging Dimensions (LxDxH)

    1220x540x1400

    mm x mm x mm

    48x22x55

    in x in x in

    Net Weight

    124

    Kg

    273

    Lb

    Gross Weight

    161

    Kg

    355

    Lb

    Notes

     

     

     

     

    DB: Outdoor Dry Bulb Temperature

    WB: Outdoor Wet Bulb Temperature

    COP: Coefficient of Performance = Heat Output in KW / Power Input in KW

    EER: Energy Efficiency Ratio = Heat Output in MBH (1000 x Btu/hr) / Power Input in KW


  • HEATING PERFORMANCE

    HSS060V2 

    Outdoor Air DB Temperature (°C)

    Outdoor Air DB Temperature (°F)

    Supply Water Temperature 95°F (35°C) / Return Water Temperature 86°F (30°C)

    Supply Water Temperature 113°F (45°C) / Return Water Temperature 104°F (40°C)

    Supply Water Temperature 131°F (55°C) / Return Water Temperature 122°F (50°C)

    Heating Capacity (KW)

    Heating Capacity (BTU/HR)

    Power in (KW)

    COP

    Heating Capacity (KW)

    Heating Capacity (BTU/HR)

    Power in (KW)

    COP

    Heating Capacity (KW)

    Heating Capacity (BTU/HR)

    Power in (KW)

    COP

     -20 

    -4

     8.54 

    29,137

    3.44

     2.48 

     7.24 

    24,702

    3.87

     1.87 

     2.17 

    7,404

    1.61

     1.35 

     -15 

    5

     11.39 

    38,861

    3.90

     2.92 

     9.66 

    32,958

    4.54

     2.13 

     5.79 

    19,755

    3.78

     1.53 

     -7 

    19.4

     14.01 

    47,800

    4.07

     3.44 

     13.60 

    46,401

    4.66

     2.92 

     12.38 

    42,239

    5.90

     2.10 

     2 

    35.6

     16.48 

    56,227

    4.41

     3.74 

     16.00 

    54,589

    4.82

     3.32 

     15.52 

    52,952

    5.71

     2.72 

     7 

    44.6

     18.50 

    63,119

    4.16

     4.45 

     17.39 

    59,332

    4.83

     3.60 

     16.52 

    56,363

    5.58

     2.96 

     12 

    53.6

     19.43 

    66,292

    4.01

     4.85 

     18.26 

    62,300

    4.57

     4.00 

     17.35 

    59,195

    5.29

     3.28 

     20 

    68

     20.40 

    69,601

    3.76

     5.43 

     19.17 

    65,405

    4.17

     4.60 

     18.21 

    62,129

    4.83

     3.77 

     


  • MANUAL