    A. General:

    • Unit is factory assembled and tested chilled and hot water fan coil.
    • Shall be assembled with high quality.
    • Contained with the unit shall be all factory wiring, piping, associated controls and special accessories required prior to start up.
    • Unit is delivered with 24V transformer and Fan relays for field installed thermostat.

    B. Unit Cabinet:

    • Composed of galvanized steel with baked polyester powder and high impact polymers.
    • Cabinet is internally insulated to ensure quiet operation.

    C. Fan Motors:

    • Is available in 208/230-1-50/60 VAC.
    • Fan motors has three speed, direct drive, and PSC type.
    • Totally enclosed.
    • Internal overload protected.
    • Unit has a swing motor to modulate the discharge air.

    D. Blower Wheels:

    • Blower wheels are tangential and dynamically balanced.

    E. Water Coil:

    • Manufactured with water coils containing 3/8” copper tubing mechanically bonded to aluminum fins.
    • Coil is factory tested to 350 psig.
    • Maximum inlet water temperature 180° F

    F. Drain Pan:

    • All drain pans is coated on both the interior and exterior with baked polyester powder to resist corrosion.
    • The exterior of all drain pans is insulated with closed cell to prevent condensation.
    • Pans contains drain tubing that is accessible from the back, bottom and side of the unit.

    G. Filters:

    • Unit contains 65% washable filters.

    I Controls & Safety:

    • Fan coils shall be completely factory wired and tested.
    • Unit shall include a terminal block that is capable of incorporating a 24 VAC thermostat. C. 
    • Controls shall be capable of incorporating an optional hard-wired thermostat.
    • Fan coil shall contain a non reusable fuse on the secondary voltage side of the transformer.
    • Electrical shall include a terminal block.
    • Electrical power supply shall be rated to withstand 120°F operating ambient temperatures.
  • technical documentsManualwiring