OXYPEX Radiant Heating Pipe

Size
Roll Length

Accepted Payment Methods:  Credit Cards paypal bank transfer

Return Policy: We accept return within 30 days of receipt of your orders. Returned Items shall have intact labels, packages and shall not have been used. for more info....

  • refund Full refund if you do not receive your ordered items. 
  • refund Partial Refund for partially not received or partially damaged items

OXYPEX Radiant Heating Pipe

Overview

BOW OXYPEX tubing is designed specifically for hydronic heating and hydronic radiant closed loop heating applications. This tubing has an oxygen outer barrier liner which makes it ideal for hydronic and radiant floor heating applications.

The function of the outer liner is to limit the oxygen permeation rate through the pipe wall. Oxypex tubing can also be used in snow melting applications. This tubing Complies with DIN 4726 as endorsed by the Hydronics Institute. Oxypex is made to CTS (Copper Tube Size) outside dimensions and an SDR (Standard Dimension Ratio) of 9 and is available in the following nominal sizes: 3/8", 1/2", 5/8" 3/4" and 1". It is available in coils up to 1200' long which are “footmarked”.

Technical Data

Material

Cross-Linked polyethylene, PEX Silane Method, EVOH Oxygen Barrier.

Continuous working pressure:

690 kPa (100 PSI) @ 82ºC (180º F), 1105 kPa (160 PSI) @ 23ºC ( 73º F).

Standards

ASTM F876; ASTM F877; CSA B137.5; DIN 4726. Compatible fittings: ASTM F1807; ASTM F2159

Listings

PDF Icon PEX Installation Manual